Water-Z Screw Compressor
SEAH INDUSRTRY
WZ Series provides purified fine "oil free" compressed air through water lubricated type.
There is no need for oil because all the parts are lubricated by only water.
High efficiency
- It guarantees lubrication, cooling, air tightness with only water.
- Air non-permeability is that water complements the fine clearance that are between rotors, therefore,
it maximizes production efficiency by over 15% compared to traditional screw rotor's oil free type.
High reliability
- Air-End that is applied to WZ Series was first introduced to the market in 1980, and ever since
it has been supplied for more than 30 years.
- External appearance, function and design are all aimed at improving the quality of air, reduction
of energy and high reliability.
Long interval maintenance period
- Ideal compressed temperature, direct driven type, precise and careful numerical control design, and
longevity of bearing can be originally more improved or extended by our regular service.
Controller
* Alarm function * Set function for operation time * Automatic diagnosis * System protection function * Abnormal driving situation record * Control for variable * LED display |
|
Air-end
* Produce highly purified compressed airr * Designed for low noise (60 ~ 68 dB) * Parts that are consisted of ceramic and carbon textiles * Ideal pressure air temperature ( below 40℃ ) * Really, there is no need for oil. * Environment friendly designed |
|
Model |
WZ-15A |
WZ-22A |
WZ-37A |
WZ-37W |
WZ-55W |
WZ-75W |
WZ-90W |
WZ-100W |
WZ-120W | |
Motor |
Hp |
20 |
30 |
50 |
50 |
75 |
100 |
120 |
135 |
160 |
kw |
15 |
22 |
37 |
37 |
55 |
75 |
90 |
100 |
120 | |
Pressure |
kg/cm2 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
Capacity |
m3/min |
2.3 |
3.5 |
6.0 |
6.0 |
9.5 |
13.0 |
15.0 |
17.4 |
20.8 |
Lubricate water |
Liter |
26 |
27 |
40 |
30 |
100 |
100 |
100 |
100 |
100 |
Discharge pipe Diameter |
inch |
1 |
1 |
1-1/4 |
1-1/4 |
2 |
2 |
3 |
3 |
3 |
(A) |
25 |
25 |
32 |
32 |
50 |
50 |
80 |
80 |
80 | |
C.W Requirement |
L/min |
Fan cooling |
125 |
190 |
250 |
250 |
270 |
320 | ||
Dimension (mm) |
Length |
1,460 |
1,460 |
1,575 |
1,575 |
2,290 |
2,290 |
2,840 |
2,840 |
2,840 |
Width |
810 |
810 |
965 |
870 |
1,230 |
1,230 |
1,630 |
1,630 |
1,630 | |
Height |
1,500 |
1,500 |
1,630 |
1,100 |
1,450 |
1,450 |
1,740 |
1,740 |
1,740 | |
Weight |
kg |
720 |
790 |
1,000 |
790 |
1,700 |
1,850 |
2,695 |
2,745 |
2,800 |
※ "C.W Requirement" is the requirement of cooling warer ( 32℃ )
※ Activating type is Star delta.
※ Power transmission is direct coupling type.
※ Exclusive use for 50 Hz is available and the products applied for inverter can be manufactured.
※ Be careful that above specification can be changeable at any time without any prior notice